Individual Functions
6-
119
Setting Motor Constants
In vector control method, the motor constants are set automatically using autotuning. If autotuning does not
complete normally, set them manually.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
E2-01
Motor rated
current
Sets the motor rated current in 1 A
units.
These set values will become the
reference values for motor protec-
tion, torque limits and torque con-
trol.
This constant is automatically set
during autotuning.
0.32 to
6.40
*2
1.90 A
*1
NoQQQQQ30EH
Motor Rated
FLA
E2-02
Motor rated slip Sets the motor rated slip in Hz
units.
These set values will become the
reference values for slip compen-
sation.
This constant is automatically set
during autotuning.
0.00 to
20.00
2.90
Hz
*1
NoAAAAA30FH
Motor Rated
Slip
E2-03
Motor no-load
current
Sets the motor no-load current in
1 A units.
This constant is automatically set
during autotuning.
0.00 to
1.89
*3
1.20 A
*1
NoAAAAA310H
No-Load Cur-
rent
E2-04
Number of
motor poles
Sets the number of motor poles.
This constant is automatically set
during autotuning.
2 to 48
4
poles
No No Q No Q Q 311H
Number of
Poles
E2-05
Motor line-to-
line resistance
Sets the motor phase-to-phase
resistance in Ω units.
This constant is automatically set
during autotuning.
0.000
to
65.000
9.842
Ω
*1
NoAAAAA312H
Term Resis-
tance
E2-06
Motor leak
inductance
Sets the voltage drop due to motor
leakage inductance as a percent-
age of the motor rated voltage.
This constant is automatically set
during autotuning.
0.0 to
40.0
18.2%
*1
No No No A A A 313H
Leak Induc-
tance
E2-07
Motor iron sat-
uration coeffi-
cient 1
Sets the motor iron saturation
coefficient at 50% of magnetic
flux.
This constant is automatically set
during rotational autotuning.
0.00 to
0.50
0.50 No No No A A A 314H
Saturation
Comp1
E2-08
Motor iron sat-
uration coeffi-
cient 2
Sets the motor iron saturation
coefficient at 75% of magnetic
flux.
This constant is automatically set
during rotational autotuning.
0.00 to
0.75
0.75 No No No A A A 315H
Saturation
Comp2
TOE-S616-60.1.book 119 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals