Verify the chassis replacement
Procedure
1. Run the disk rescan command to discover the disks.
a. If all of the disks are not listed, perform another rescan.
b. If all of the disks are still not listed, check the connection.
2. Enter the alerts show current command and confirm that the system has
no alerts.
# alerts show current
No active alerts.
If the command output displays hardware failure, use the appropriate sections
in this document (PSU, , disk, and fan) to identify and verify the component
connections until there are no alerts.
Installing the front bezel
Procedure
1. Align the bezel with the shelf.
2. Gently push the bezel into place on the cabinet until it latches.
3. If the bezel has a key lock, lock the bezel the provided key.
DS60 bezel replacement
This procedure describes how to remove and replace the 4U DS60 bezel.
Removing the front bezel
You must remove the front bezel to gain access to the internal components. The bezel
is required for EMI compliance when the shelf is powered up. Remove it only to
replace or add an internal component.
Procedure
1. If the bezel has a lock, insert the key that shipped with your shelf into the lock,
and turn the key to unlock the bezel.
2. Press the two latch buttons on the bezel surface to release the bezel from the
cabinet.
3. Pull the bezel off the cabinet and put it on a clean, static-free surface.
Removing and Replacing FRUs