EasyManuals Logo
Home>Honeywell>Control Systems>AUTOMATIC CONTROL SI Edition

Honeywell AUTOMATIC CONTROL SI Edition User Manual

Honeywell AUTOMATIC CONTROL SI Edition
512 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #239 background imageLoading...
Page #239 background image
ENGINEERING MANUAL OF AUTOMATIC CONTROL
AIR HANDLING SYSTEM CONTROL APPLICATIONS
229
FEATURES
1. Preheat coil conditions large quantities of low temperature
OA before it enters the system.
2. Bypass damper controls temperature of air leaving the
face-and-bypass section without endangering the preheat
coil which operates in full valve open mode during
freezing conditions.
3. Upon fan shutdown, valve controls at 38°C leaving air
temperature in freezing weather and positions closed upon
fan shutdown in non-freezing weather.
CAUTION: If steam (or very hot water) valves position
full open during off periods, air tempera-
tures may melt fire damper linkages.
CONDITIONS FOR SUCCESSFUL OPERATION
1. Preheat coil sized to raise a maximum quantity of OA
from outdoor design temperature to 10°C.
2. Averaging element sensor positioned in face-and bypass
air to sense average air temperature.
3. Bypass air well mixed with face (and return) air prior to
entering down-stream water coils (additional low
temperature controls may be required for down-stream
water coils).
4. On large 100% OA systems the OA damper opens prior
to fan start up to protect ducting from collapse.
5. The setpoint of air leaving the preheat section is usually
dictated by the downstream AHU temperature controls.
SPECIFICATIONS
See FAN SYSTEM START-STOP CONTROL.
Anytime the supply fan runs, heating control shall be enabled,
and the OA dampers shall open for ventilation requirements.
The heating coil valve shall open upon loss of actuator motive
force, shall close upon fan shutdown if the OA temperature is
above 1.5°C, and shall control to maintain 38°C leaving air
temperature upon fan shutdown if the OA temperature is below
1.5°C.
The heating coil valve shall position from 0 to 100% open as
the OA temperature varies from 10°C to 1.5°C. The face-and-
bypass dampers shall modulate to maintain an average face-
and-bypass leaving air temperature of 10°C.
PSYCHROMETRIC ASPECTS
In the following chart it is assumed that:
1. The coil has a temperature rise of 28 kelvins with full air
flow –18°C air and a temperature rise of 39 kelvins with
reduced air flow as in the example.
2. The coil water flow modulates from closed to open as
OA temperature drops from 10°C to 1.5°C.
3. OA temperature is –1°C DB.
The following results are obtained:
Item
No. Explanation
1 Heating of OA occurs along a line of constant
moisture content from –1°C to 38°C.
2 The PID control loop maintains the
temperature of the preheat section leaving air.
C3242
AIR LEAVING
PREHEAT
SECTION
AIR LEAVING
HEATING COIL
38°C DB
1
2
OA AND AIR
LEAVING BYPASS
SECTION -1°C DB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AUTOMATIC CONTROL SI Edition and is the answer not in the manual?

Honeywell AUTOMATIC CONTROL SI Edition Specifications

General IconGeneral
BrandHoneywell
ModelAUTOMATIC CONTROL SI Edition
CategoryControl Systems
LanguageEnglish

Related product manuals