EasyManuals Logo
Home>Honeywell>Control Systems>AUTOMATIC CONTROL SI Edition

Honeywell AUTOMATIC CONTROL SI Edition User Manual

Honeywell AUTOMATIC CONTROL SI Edition
512 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #428 background imageLoading...
Page #428 background image
ENGINEERING MANUAL OF AUTOMATIC CONTROL
INDIVIDUAL ROOM CONTROL APPLICATIONS
418
Thr ee room temper atur e setpoints ar e shown, free cooling, a
heating deadband , and a mec hanical cooling deadband . The fr ee
cooling setpoint ma y be man ual on the w all module , or softw ar e
(with softw ar e bounds). All unit v entilator s are switched to the
free cooling economiz er mode of oper ation globall y anytime the
OA is suita ble (see the Air Handling System Contr ol Applica tions
section). When the O A is unsuita ble for fr ee cooling assistance ,
and c hilled water is a vailable, the OA damper is r etur ned to the
minim um ventila tion.
PRECAUTIONS AND CONDITIONS FOR
SUCCESSFUL OPERATION
Unit ventilator s requir e protection fr om blocked airf low,
power failur e, and coil fr eeze-up.
Blocked Airflow
Pr oper airf low is essential to sa tisfying space temper atur e
and v entila tion r equir ements. Objects loca ted dir ectly over the
dischar ge air v ents can inhibit or b lock airf low. Cleaning or
replacing the f ilter as needed and c leaning dust and dir t fr om
unit v entila tor coils impr oves airf low thr ough the unit v entila tor.
Power Failure
Pr ecautions f or po wer and air f ailur e must be specif ied when
the automatic control system is designed. Pneumatic systems
requir e an electr ic-pneuma tic switch to exhaust the v alve and
damper actua tor dia phr agms on a po wer or air f ailur e. The outdoor
air damper c loses and the r etur n air damper and coil v alve open.
Electr ic, electr onic, and dig ital contr ol systems should be specif ied
with spring-return actuators that close the outdoor air damper and
open the r etur n air damper on po wer failur e.
Coil Freeze-Up
Causes of coil freeze-up include central system circulating
pump or boiler f ailur e, outdoor air damper or contr ol valve
malfunction, and une ven temper atur e distr ibution. A low-limit
contr oller can help pr event coil fr eeze-up b y overriding other
control system components to close the outdoor air damper
and open the r etur n air damper and coil v alve. Effective freeze-
up pr otection de pends on a vailable heat in the system and f low
through the coils.
Coils can also fr eeze when low-temper atur e outdoor air leaks
thr ough def ective damper s. Frequent inspection of damper s
should be made to detect bent and br oken damper linka ges,
war ped damper b lades, and def ective or missing b lade seals
tha t can contr ibute to coil fr eeze-up.
Low temper atur e switches to stop the f an and c lose the OA
damper should be pr ovided wher e freezing OA conditions ar e
likely. With dig ital systems, dur ing unoccupied per iods, the low
temper atur e switch ma y star t the f an and the r ecircula ting pump.
FAN COIL UNITS
GENERAL
Fan coil units ar e similar to unit v entila tor s except tha t fan
coil units do not ha ve damper s and typicall y do not ha ve an
outdoor air intak e. They may also be conf igured for installa tion
above a ceiling with ceiling or w all mounted disc har ge and
retur n air g rills. Fan coil units pr ovide hea ting and/or cooling
for single-z one ar eas such as a par tments, offices, and indi vidual
hotel or hospital r ooms. Figure 30 shows a typical f an coil unit
compr ising a finned-tube coil, a fan section, and a f ilter. The
fan cir culates air fr om the space acr oss the coil. The coil ma y
use steam or hot w ater fr om a centr al system or electr ic
resistance elements to satisfy heating requirements. Chilled
water or DX coils can be used f or cooling . Units used f or cooling
only or for both hea ting and cooling ha ve a built-in condensa te
dr ain pan to collect and dr ain condensa te on the cooling c ycle.
Fig. 30. Fan Coil Unit.
Fan coil units ar e classified as two-pipe hea ting, two-pipe
cooling, two-pipe hea ting/cooling , or four-pipe hea ting/cooling .
Contr ol for a f an coil unit typicall y compr ises a r oom or r etur n
air ther mosta t for indi vidual r oom contr ol. The ther mostat
regulates a valve while a fan moves air thr ough the unit and
across the coil. The fan r uns contin uously, is scheduled , or is
cycled on and of f by the ther mosta t. The fan is often thr ee speed
with a local three-speed switch. Some applications control only
the fan oper ation and allo w the conditioning medium to f low
continuously in the coil. F an coil units can use pneuma tic,
electric, electronic, or digital control.
C3038
DISCHARGE
AIR
WALL
OUTDOOR
AIR
(OPTIONAL)
RETURN
AIR
FILTER
COIL
FAN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AUTOMATIC CONTROL SI Edition and is the answer not in the manual?

Honeywell AUTOMATIC CONTROL SI Edition Specifications

General IconGeneral
BrandHoneywell
ModelAUTOMATIC CONTROL SI Edition
CategoryControl Systems
LanguageEnglish

Related product manuals