EasyManuals Logo
Home>Honeywell>Control Systems>AUTOMATIC CONTROL SI Edition

Honeywell AUTOMATIC CONTROL SI Edition User Manual

Honeywell AUTOMATIC CONTROL SI Edition
512 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #472 background imageLoading...
Page #472 background image
ENGINEERING MANUAL OF AUTOMATIC CONTROL
DAMPER SELECTION AND SIZING
462
DAMPER PRESSURE DROP
If the duct size, damper size, and the airflow are known, use
the method in Table 6 to determine the actual pressure drop
across the damper:
For example, for a 1.50 m
2
parallel blade
damper in a 1.69 m
2
duct with an airflow of 9.45 m
3
/s, determine the pressure drop
across the damper as shown in Table 7.
Table 6. Damper Pressure Drop Calculation Procedures
Step Procedure
1 a. Determine the number of sections required.
The area of the damper must not exceed the maximum size for a single section. If the damper area exceeds the
single section area:
b. Divide the area of the damper, the area of the duct, and the airflow by the number of damper sections.
c. Use the values from Step b in the following Steps.
2
Calculate the free area ratio
a
:
For parallel blade dampers, the free area ratio is found:
Ratio = (0.0798 x damper area m
2
)
0.1007
x
Damper area (m
2
)
Duct area (m
2
)
For opposed blade dampers, the free area ratio is found:
Ratio = (0.0180 x damper area m
2
)
0.0849
x
Damper area (m
2
)
Duct area (m
2
)
3 Using the ratio from Step 1, calculate the pressure drop at 5.08 m/s.
For ratios ≤ 0.5:
Pressure drop (Pa) = –11.64 x (1 – ratio
–2.562
)
For ratios > 0.5:
Pressure drop (Pa) = –3.114 x (1 – ratio
–4.274
)
4 Calculate the approach velocity:
Approach velocity (m
3
/s) =
Airflow (m
3
/s)
Duct Area (m
2
)
5 Using the approach velocity from Step 3, calculate a correction factor:
Correction factor =
25.8
[Approach velocity (m/s)]
2
6 Calculate the pressure drop across the damper:
Pressure drop (Pa) =
Pressure drop (Pa) at 5.08 m/s (Step 2)
Correction factor (Step 4)
a
The free area of a damper is the open portion of the damper through which air flows. The free area ratio is the open area in
a damper divided by the total duct area.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AUTOMATIC CONTROL SI Edition and is the answer not in the manual?

Honeywell AUTOMATIC CONTROL SI Edition Specifications

General IconGeneral
BrandHoneywell
ModelAUTOMATIC CONTROL SI Edition
CategoryControl Systems
LanguageEnglish

Related product manuals