Operation - Stream Configuration
Part No.: 4418309_Rev09 Fusion4 MSC-L
Honeywell Installation & Operation Manual 5 - 149
The hydraulic pump is de-activated when the batch stops and
[Hydraulic pump run timeout] elapses.
5.14.1.3 Stream Config. . Stream n . Control Settings
On the Stream Config . Stream n screen, select <Control settings>.
The Stream Config . Stream n . Control Settings screen is displayed
with the following entities.
5.14.1.3.1 Product Control
On the Stream Config . Stream n . Control Settings screen, select
<Product control>.
The Stream Config . Stream n . Product Control screen is displayed
with the following entities.
Entity Description Value range
[Dead band (kdb)]
With this entity you can configure the
allowed flow deviation from the target
flow. When the actual flow is less than
the [Dead band] limit, the control output
from the controller is locked. Changes
are not made to the product stream
control valve. This value effectively
establishes the dead band in which the
product stream flow can deviate
without correction.
The dead band defines this value.
default =
<15> liters
[Feed forward (kff)]
This entity is used only for non-DCV
type valves.
default = <0.00>
[Integral (ki)]
With this entity the Integral part of the
PI(D) controller can be set.
default = <0.00>