Alarm Handling - List of all alarms
Part No.: 4418309_Rev09 Fusion4 MSC-L
Honeywell Installation & Operation Manual 6 - 11
6.8.3 Arm Alarms
Alarm Cause
Initial flow rate low The flow rate during the initial flow stage is below the arm
initial flow rate by the
[Low percentage] after the [Alarm start
delay] elapsed.
Initial flow rate high The flow rate exceeds the arm initial flow rate by the
[High
percentage] and the [Alarm start delay] elapsed.
Full flow rate low The full flow rate is below the arm full flow rate by the
[Low
percentage]
and the [Alarm start delay] elapses.
Full flow rate high The flow rate exceeds the arm full flow rate by the
[High
percentage]
and the [Alarm start delay] elapses.
Pre-stop flow rate low The flow rate during the pre-stop flow stage is below the arm
pre-stop flow rate by the
[Low percentage] and the [Alarm
start delay] elapses.
Pre-stop flow rate high The flow rate during the pre-stop flow rate exceeds the arm
pre-stop flow rate by the
[High percentage] and the [Alarm
start delay] elapses.
Programmable input
1..6
The programmable input state (active/de-active) does not
match with the expected input state.
Block valve fault No valve feedback is detected.
Arm exceeds overrun
limit
The measured volume exceeds the preset and the
configured overrun limit.
Clean arm volume not
reached
The measured clean arm volume is less than the specified
clean arm volume minus the clean arm tolerance.
Arm parked The arm parked input is detached.
Batch initialization
error
A problem inside the device prohibits the batch to be initial-
ized.
Calibration batch ini-
tialization error
A problem inside the device prohibits the calibration batch to
be initialized.
Batch start error A problem inside the device prohibits the batch to be
started.
Calibration batch start
error
A problem inside the device prohibits the calibration batch to
be started.
Batch stop error A problem inside the device prohibits the batch to be
stopped.
Calibration batch stop
error
A problem inside the device prohibits the calibration batch to
be stopped.
Batch pause error A problem inside the device prohibits the batch to be
paused.
Batch resume error A problem inside the device prohibits the batch to be
resumed.