Operation - Stream Configuration
Part No.: 4418309_Rev09 Fusion4 MSC-L
Honeywell Installation & Operation Manual 5 - 189
5.14.3.2 Stream Config - Ext add n - Alarms
1. On the Stream Config - Ext add n screen, select <Alarms>. The
Stream Config - Ext add n - Alarms screen appears with the
following entities.
2. On the Stream Config - Ext add n - Alarms screen, select <Fixed>.
The following screen appears with the fixed alarms.
Entity Description Value range
<External additive name>
With this entity you can enter the name
of the additive product.
A text string of maximum 12 characters.
Use maximum 7 characters to view the
complete name on the MSC-L display
screen.
<COM port>
With this entity you can configure the
<COM port> to be used for
communicating with the external
additive controller.
<COM1>or <COM2> for streams on Arm
board 1 (Streams 1 to 12)
<COM6>or <COM7> for streams on Arm
board 2 (Streams 13 to 24)
<Stream Address>
With this entity you can configure the
<Stream Address> for the external
additive streams.
<0> ... <999>