Technical data
Rated data
Operation at 480 V
3
137
EDKVS9332X DE/EN/FR 8.0
3.3.2 Operation at 480 V
Basis of the data
Voltage Frequency
Supply
3/PE 480 V AC [U
r
] 320 V − 0 % ... 528 V + 0 % 45 Hz − 0 % ... 65 Hz + 0 %
DC 678 V (alternatively) [U
DC
] 460 V − 0 % ... 740 V + 0 % ˘
Output voltage
With mains choke 3 ~ 0 ... approx. 94 % U
r
˘
Without mains choke 3 ~ 0 ... U
r
˘
9300 Mains current
1)
Typical motor power Output power Power loss
With
mains choke
Without
mains choke
ASM
(4−pole)
8 kHz
2)
U, V, W +U
G
, −U
G
3)
Type I
r
[A] I
r
[A] P
r
[kW] P
r
[hp] S
r8
[kVA] P
DC
[kW] P
V
[W]
EVS9321−xx 1.5 2.1 0.37 0.5 1.2 2.0 100
EVS9322−xx 2.5 3.5 0.75 1.0 2.1 0.75 110
EVS9323−xx 3.9 5.5 1.5 2.0 3.2 2.2 140
EVS9324−xx 7.0 ˘ 3.0 4.0 5.8 0.75 200
EVS9325−xx 12.0 16.8 5.5 7.5 10.8 0 260
EVS9326−xx 20.5 ˘ 11.0 15.0 18.5 0 390
EVS9327−xx 27.0 43.5 18.5 25.0 25.0 12 430
EVS9328−xx 44.0 ˘ 30.0 40.0 37.0 4.8 640
EVS9329−xx 53.0 ˘ 37.0 50.0 46.6 0 810
EVS9330−xx 78.0 ˘ 45.0 60.0 69.8 6 1100
EVS9331−xx 100 ˘ 55.0 75.0 87.3 0 1470
EVS9332−xx 135 ˘ 90.0 125 104 6 1960
Bold print = Lenze setting
1)
Mains currents at 8 kHz switching frequency
2)
Switching frequency of the inverter
3)
Power which can additionally be drawn from the DC bus at operation with power−adapted motor