Description of the blocks
4.3 MMOprtn block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
103
4.3.4
Motor current
The motor current is transferred via the input parameter PZDIn23 as an unsigned 2-byte
value. SIMOCODE pro always transfers the current here as a percentage of the set current
in a range from 0 to 1020%.
The
MotCurr parameter calculates this as a percentage.
The
MotCurrE parameter calculates the motor current actually drawn in amps based on the
set current for the motor configured in SIMOCODE.
Note
The motor current is only calculated if the current measuring module is connected to the
SIMOCODE
pro device and configured.
4.3.5
Device functions
Parameter DevFunc
The DevFunc parameter provides information about the parameterization of SIMOCODE pro
and the configuration of further modules by reading the DS105. The data are relevant for:
Device class
Control function
Status thermistor
Status analog module
Status temperature
Status ground fault module
Status voltage module
Current measuring module
Analog module
Digital module
The structure of the
DevFunc parameter can be found in the UDT "OPERATION".

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals