Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
218 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
4.7.22 Status information
The status information is passed to WinCC for display in the faceplates.
Status1
Table 4- 104 Status1 – MMRevDhl
Status1
bit
Description
0 Occupied
1 BatchEn
2 Set the Simulation bit On
6 1 = Local Active
7 0 = Open padlock in the block icon
1 = Closed padlock in the block icon
8 1 = Fwd Command
9 0 = Stop Command
1 = Run Command
10 1 = Rev Command
11 1 = FFwd Command
12 1 = FRev Command
13 1 = Static Monitoring Error
14 1 = Dynamic Monitoring Error
15 Cross pad protection inputs
16 Invalid signal status
17 Error in mode change
18 1 = Intlock is active
19 1 = Permit is active
20 1 = Protect is active
21 Trip.Value
22 FwdForce
23 StopForce
24 RevForce
25 Fast FwdForce
26 Fast Reverse Force
27 "Interlock" button activated
28 Reset request with input signal
29 WarnAct.Value or IdleTime is active
30 Bypass information from previous function block
31 "Permission" button is enabled