Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
93
Forcing operating modes in the "Local" mode
Number of the Feature2 bit: 8
Specify whether forcing operating modes is possible in the "Local" mode.
The default setting is 0.
: In the "Local" mode, forcing operating modes is not possible.
: In the "Local" mode, forcing operating modes is possible.
Considering bad quality of automatic commands or external values
Number of the Feature2 bit: 10
Use this bit to consider the bad signal status (16#00 or 16#28) in the parameter for the
automatic commands or external values to move the block into the neutral position.
The default setting is 0.
: The bad signal status will not be considered.
: The bad signal status (16#00 or 16#28) in the automatic commands or external values
will be considered from the block. The block goes to a defined neutral position.
Separate interlock for each direction or position
Number of the Feature2 bit: 16
To enable the use of the "Separate interlock for each direction or position" function.
The default setting is 0.
One interlock for each direction or position.
Separate interlock for each direction or position.