Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
212 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
4.7.14
Disabling interlocks
Disabling individual interlocks
You can disable the block interlocks that are implemented using the input parameters
Permit, Intlock and Protect.
This is done by setting the following parameters:
Perm_En = 0 or Permit.ST = 16#FF: The Permit input parameter has no effect
Prot_En = 0 or Protect.ST = 16#FF: The Protect input parameter has no effect
Intl_En = 0 or Intlock.ST = 16#FF: The Intlock input parameter has no effect
Deactivation of all interlocks
You can use the input parameter BypProt = 1 to disable all the interlocks, irrespective of the
parameter assignment of the individual interlock, in local mode as well as for the "simulation"
function.
4.7.15
Group fault
GrpErr
The output parameter for group error GrpErr is set when one of the errors listed below is
detected.
The STANDARD view displays these errors as a "group error" in plain text.
Control System Fault (
CSF)
Trip (
Trip)
Feedback error due to control change (
MonDynErr)
Feedback error due to unexpected feedback change (
MonStaErr)

Table of Contents

Other manuals for Siemens SIMOCODE pro

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000

Summary

Introduction

Security information

Discusses Siemens' commitment to industrial security and customer responsibilities.

Components of the software package

Lists the blocks and other components included in the SIMOCODE pro PCS 7 Library V9.0.

Configuration Steps

Details the procedures for configuring SIMOCODE pro devices in HW Config and CFC.

Driver generator

Explains the function and purpose of the driver generator for signal processing in PCS 7.

Templates

Overview of the templates, control functions and blocks

Introduces templates for adopting control functions and lists associated blocks.

Using templates

Explains how to instantiate and interconnect templates within the SIMOCODE pro Library in CFC.

Block icons and faceplate views

Faceplates

Explains the structure, navigation, and views (Batch, Trend, Alarm, Preview) of SIMOCODE pro faceplates.

Description of the blocks

Diagnostics block MMDiag

Details the MMDiag block's purpose, messages, and driver generator integration.

MMOprtn block

Provides an overview of the MMOprtn block, its purpose, views, and parameters.

Block for MMMeas measured value function

Describes the MMMeas block for gathering measured value parameters and diagnostic data.

MMRevDhl motor block

Covers the MMRevDhl block for controlling Dahlander High Feature reversing starters.

Parameter

Block parameter MMOprtn

Details input and output parameters for the MMOprtn block.

Block parameter MMRevDhl

Details input and output parameters for the MMRevDhl block.

Related product manuals