Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
212 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Disabling interlocks
Disabling individual interlocks
You can disable the block interlocks that are implemented using the input parameters
Permit, Intlock and Protect.
This is done by setting the following parameters:
●
Perm_En = 0 or Permit.ST = 16#FF: The Permit input parameter has no effect
●
Prot_En = 0 or Protect.ST = 16#FF: The Protect input parameter has no effect
●
Intl_En = 0 or Intlock.ST = 16#FF: The Intlock input parameter has no effect
Deactivation of all interlocks
You can use the input parameter BypProt = 1 to disable all the interlocks, irrespective of the
parameter assignment of the individual interlock, in local mode as well as for the "simulation"
function.
The output parameter for group error GrpErr is set when one of the errors listed below is
detected.
The STANDARD view displays these errors as a "group error" in plain text.
● Control System Fault (
CSF)
● Trip (
Trip)
● Feedback error due to control change (
MonDynErr)
● Feedback error due to unexpected feedback change (
MonStaErr)