Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
86 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Activate fault status for external control system fault
Number of the Feature bit: 18
Specify whether the block should switch to the error state at an external process control error
CSF =1.
The default setting is 0.
Block does not go to error state with process control error CSF = 1.
Activated: Block goes to error state with process control error CSF = 1.
Reset even in locked state
Number of the Feature bit: 19
You can specify if it is possible to perform a reset with an active "Protection" or "Motor
protection" type interlock. This can be used, for example, to reset hardware interlocks.
The default setting is 0.
No reset is possible with a "Protection" type interlock or with active motor protection.
Reset is possible with a "Protection" type interlock or with active motor protection.
Disable Feedback Tracking LocalSetting 2 & 4
Number of the Feature bit: 20
To disable the tracking of feedback signals in the "Local" mode setting 2 and 4.
The default setting is 0.
Calculation of impulse controls in LocalSetting 2 and 4.
Disable calculation of impulse controls in LocalSetting 2 and 4.