Introduction
1.10 Update an existing PCS 7 project
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
37
Assignment of the PROFIsafe address
Each DM-F PROFIsafe fail-safe digital module has its own PROFIsafe address. You must
set the PROFIsafe address on the module prior to commissioning.
The PROFIsafe addresses (
F_Source_Add, F_Dest_Add) are automatically assigned when you
configure the DM-F PROFIsafe module in STEP 7.
You can find the PROFIsafe address that must be set on the DM-F PROFIsafe module in the
HW Config under the object properties for the PROFIsafe module; it is shown in decimal and
hexadecimal notation in the
F_Dest_Add parameter. Convert this address to binary notation
and set it via the DIP address switch on the DM-F PROFIsafe module.
Enter an icon for the fail-safe output in HW Config. In conjunction with F systems, this icon is
then connected in CFC with the fail-safe channel driver (output VALUE). When integrating
SIMOCODE pro V with GSD file via the Object Manager (OM), the F_CH_BO block is used
as the channel driver.
Refer to the system manual "SIMOCODE pro Safety - fail-safe digital modules
(https://support.industry.siemens.com/cs/document/50564852
)" for more information on
using the fail-safe digital modules.
Update an existing PCS 7 project
Performing a project update
Refer "ReadMe" provided with the library.
Further documentation
Overview
More information
● Online help for PCS 7 Advanced Process Library
● Online help for SIMATIC PCS 7 Process Control System
● Function manuals for SIMATIC PCS 7 Process Control System on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/109482346
)
● System Manual SIMOCODE pro PROFINET on the Internet
(https://support.industry.siemens.com/cs/document/61896631
)
● Getting Started on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/109482390
).