Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
209
Reference
MMRevDhl - Maintenance (Page 225)
4.7.12
Motor Protection
The motor protection function is used to switch off the motor on a thermal overload
(
Trip = 0, interconnectable input parameters).
If the motor is switched off via the motor protection function, a message is generated
(process control message). This is displayed in the faceplate with the text "Motor protection."
You can influence the reset via various Feature.Bits. For more details, refer to the section
5.6.3 "Resetting the block in case of interlocks or errors" .
4.7.13
Interlocking
Interlocks
This block provides the following interlocks:
Feature 2 bit 16 = 0:
Activation enable
Interlock without reset ("Interlock")
Interlock with reset ("Protection")
Feature 2 bit 16 = 1:
Activation enable forward
Activation enable reverse
Interlock forward without reset ("Interlock forward")
Interlock reverse without reset ("Interlock reverse")
Interlock forward with reset ("Protection interlock forward")
Interlock reverse with reset ("Protection interlock reverse")

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals