Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
81
Set startup characteristics for motors
Bit = 0:
Starting the block in manual mode and in neutral position. With controllers, the
setpoint is set to (SP_Int) internally.
Starting the block with the last stored values, in other words in the last operating
mode set (manual, automatic or local mode) and at the last valid position.
Note
Special note following complete download to the CPU
F
ollowing a complete download to the CPU, the motor protection signal Trip is evaluated
during the initial run as good (=1). When a motor protection signal is pending, this causes a
non
-struck-through message with time stamp and auxiliary values beginning with RunUpCycle
after the complete download and after expiration of the RunUpCycle
counter.
Response for Out of service mode
Number of the Feature bit: 1
Define the reaction of the technologic block based on the interconnectable input parameter
OosLi = 1.
The default setting is 0.
The symbol for the "In progress" status appears in the block icon and in the faceplate
of the assigned technologic block. A 0-1 edge transition at the input parameter
OosLi has no
further influence on the reaction of the technological block; the previous status is retained.
No switch to the "Out of service" mode is performed.
The mode switches to "Out of service" assuming that the block is "On" or "Manual"
mode. If this is not the case, the mode does not change. The symbol for the "In progress"
status also appears in the block icon and in the faceplate of the assigned technologic block
regardless of the mode change. If no message display on the faceplate then this indicates
whether the mode change has occured or not.
Resets the commands for switching between modes
Number of the Feature bit: 2
Define how the block handles the incoming control commands AutModLi and ManModLi .
The default setting is 0.
The control commands are not reset by the block. If there are two pending control
commands for changing mode, the mode is not changed. In this case, the note text "Invalid
command" is displayed in the faceplate.