Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
84 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Bit = 1:
Direct changeover is enabled.
You can reverse the motor direction directly. The motor block reverses the direction
automatically. The motor is stopped and is started in the other direction when the time set in
the
IdleTime parameter has elapsed.
4.1.10.8
Resetting via input signals in the event of interlocking (Protection) or errors
Number of the Feature bit: 9
Feature bit purpose
Define how automatic control is to be re-enabled after an active interlock.
The default setting is 0.
Bit = 0:
After an interlock (only Protection: Input parameter Protect) or errors, the system can
only be restarted using a reset command. Reset is initiated either by operator input in the
faceplate or via the interconnectable input parameter (
RstLi = 1) in the block. Thereafter, the
currently pending command takes effect in automatic mode.
Bit = 1:
It is also possible to reset with a 0-1 edge change in the control signal in automatic
mode.
4.1.10.9
Exit local mode
Number of the Feature bit: 10
Feature bit purpose
Define how "Local mode" is either exited or will be exited with LocalSetting = 1 or
LocalSetting = 2 and if the mode is not specified by
AutModLi or ManModLi.
The default setting is 0.
Bit = 0:
Exiting local mode in manual mode (bumpless because the control signals are
continuously adjusted).
Bit = 1:
When local mode is exited, the mode changes back to the last mode that was active
prior to local mode (not bumpless).
4.1.10.10
Enable runtime for feedback signals
Number of the Feature bit: 11
Feature bit purpose
To activate the runtime of feedback signals.
The default setting is 0.
Bit = 0:
Deactivated: Tracking of feedback for simulation immediately after the trigger signal.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals