Description of the blocks
4.6 Block for timestamping MMLog
SIMOCODE pro PCS 7 Library V9.0
188 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
4.6.5
Messages
The following application is only available for SIMOCODE pro PROFIBUS devices (Slv_Typ
= 0
).
Signal messages and special messages
SIMOCODE detects three message buffers: DS12, DS13, and DS14. Each of these data
sets has 180 bytes to contain 16 messages.
Table 4- 84 Assignment
Byte.Bit
Description
Size
0.0
Signal message or special message 1
12 bytes
12.0 Signal message or special message 2 12 bytes
24.0
Signal message or special message 3
12 bytes
…
…
…
180.0
Signal message or special message 16
12 bytes
Structure of a signal message
Table 4- 85 Signal message assignment
Byte.Bit
Description
Type
IDs (important for SIMOCODE-III)
0.0 Slot number of mod-
ule
Byte[1] 0x01: DPV1 slot model
0x04: S7 slot model
1.0 Channel number of
module
Byte[1] 0x00 .. 0x07: Number of timestamping - Input
2.0 Signal status Byte[1] Bit 7:
1 = input signal = rising edge
0 = output signal = falling edge
Bit 6:
0 = Not used
3.0
Reserved
Byte[1]
0x00
4.0 Time Byte[8] Bit 0:
1 = Clock is synchronized,
0 = Clock is not synchronized
Up to 8 signal messages can be configured via SIMOCODE ES or EDD. To display the
signal messages, the timestamping must be activated in SIMOCODE ES or EDD.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals