EasyManuals Logo
Home>Siemens>Control Unit>SIMOCODE pro

Siemens SIMOCODE pro User Manual

Siemens SIMOCODE pro
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #189 background imageLoading...
Page #189 background image
Description of the blocks
4.6 Block for timestamping MMLog
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
189
Structure of a special message
Special messages are predefined. There are 5 special messages that are displayed,
depending on the alarm type.
Table 4- 86 Special message assignment
Byte.Bit
Description
Type
IDs (important for SIMOCODE-III)
0.0 Slot number of mod-
ule
Byte[1] 0x0: DPV1 slot model
0x02: S7 slot model
1.0 Specifier of the spe-
cial message
Byte[1] 0x01: Start-up data
0x02: Time-of-day frame failure
0x04: Time difference between frame and inter-
nal clock > 1 second
0x05: STOP of functionality and timestamping
0x06: Buffer full
2.0 Feature of the special
message
Byte[1] 01h: START / INCOMING
00h: END / OUTGOING
3.0
Reserved
Byte[1]
0x00
4.0 Time Byte[8] Total time according to ISP (Internet Service
Provider) process:
Bit 0:
1 = Clock is synchronized,
0 = Clock is not synchronized

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals