Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
90 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Set reset depending on the LiOp parameter (counter blocks)
This feature bit can also be used to determine whether the setting or resetting to a default
value should be made dependent on the
LiOp parameter.
The default setting is 0.
Setting or resetting to a default value does not depend on the LiOp parameter.
Setting or resetting to a default value depends on the LiOp parameter.
LiOp = 0: Setting or resetting to a default value can only be made via the faceplate or at the
parameter for the faceplate.
LiOp = 1: Setting or resetting to a default value can only be made at the parameter for
interconnections.
Enable reset of interlocks in manual mode
Number of the Feature bit: 31
Specify whether a reset is necessary once the "Protection" interlock signal, feedback errors
("Runtime error", "Control deviation"), or "Motor protection" are present again. See also the
following section, 'Resetting the block in case of interlocks or errors' (Page 84).
The default setting is 0.
No reset required in manual mode.
Reset required in manual mode. The reset is performed using the "Reset" button
(
RstOp = 1) or, in CFC, using the input parameter RstLi.
p is unlocked for all operating modes using the "Reset" button in the faceplate
); in CFC it is unlocked using the
= 1 input parameter.
Note
The local operating mode has a separate reset mechanism.