Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
213
User-defined auxiliary values and user-defined status
For the MMRevDhl block, auxiliary values and status bits are available that are displayed in
the Standard view and that the user can define.
User-defined auxiliary values
Use the auxiliary values to display values such as motor velocity, temperature.
To do so, connect the value to be displayed with input parameters
UserAna1 or UserAna2.
In the CFC chart, you can define the text for the displayed values in the object properties of
the block (Connections > Identifiers).
Use the UserStatus parameter to display information using user-defined status bits.
To do so, connect the signal (byte) to be displayed with the
UserStatus input parameter.
The alarms are output using the ALARM_8P function.
Block messages can be enabled or disabled using the
MsgLock input.
The alarms are also suppressed if the block is in Out of service mode.
The alarms are suppressed on warm restart for the number of cycles set for power up in the
RunUpCyc parameter.