Introduction
1.5 Configuration Steps
SIMOCODE pro PCS 7 Library V9.0
16 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
The two bytes of the process image inputs (PII) are transferred from the SIMOCODE device
based on the logical address configured for the module. This is a manual configuration that a
user has to configure.
Configuring with HW Config:
1. Configure the SIMOCODE pro device at HW config.
2. Open CFC-Editor.
3. If not yet done, instantiate an appropriate template and open it.
4. Refer to the input address of the SIMOCODE pro device at HW Config and assign this
address to the textual interconnection "Input WORD address of SIMOCODE pro Module
(IW x)".
Compile the CFC chart using the "Generate Module Driver" function.
Additional information is available in the "Process Control System PCS 7 Compendium
Part A - Configuration Guidelines" Operating Manual on the Internet
(https://support.industry.siemens.com/cs/document/63187279
).