Description of the blocks
4.3 MMOprtn block
SIMOCODE pro PCS 7 Library V9.0
134 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
DiagEvt1, DiagEvt2, DiagEvt3 – event diagnostics
Table 4- 43 DiagEvt1 – event diagnostics for SIMOCODE pro devices
Bit
Meaning
0
Pre-Warning overloaded
1 Unbalance
2
Overload
3
Overload and loss of phase
4
Internal earth fault
5
External earth fault
6
Warning external earth fault
7
Thermistor trip level
8
Thermistor short circuit
9
Thermistor open circuit
10
TM1 warning level T >
11
TM1 trip level T >
12
TM1 sensor fault
13
TM1 out of range
14
Warning level I >
15
Warning level I <
16
Warning level P >
17
Warning level P <
18
Warning level Cos-Phi <
19
Warning level U <
20
AM1 warning level 0/4-20mA >
21
AM1 warning level 0/4-20mA <
22 Trip level I >
23
Trip level I <
24 Trip level P >
25
Trip level P <
26
Trip level Cos-Phi <
27
Trip level U <
28
AM1 trip level 0/4 - 20 mA>
29
AM1 trip level 0/4 - 20 mA<
30
Stalled rotor
31
No start possible

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals