Description of the blocks
4.3 MMOprtn block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
137
DiagWrn1, DiagWrn2 – Warning diagnostics
Table 4- 47 DiagWrn1 – Warning diagnostics for SIMOCODE pro devices
Bit
Meaning
0
Pre-warning overloaded
1 Unbalance
2
Overload
3
Overload and loss of phase
4
Internal earth fault
5
External earth fault
6
Thermistor trip level
7
Thermistor short circuit
8
Thermistor open circuit
9
TM1 level T >
10
TM1 sensor fault
11
TM1 out of range
12
Level I >
13
Level I <
14
Level P >
15
Level P <
16
Level Cos-Phi <
17
Level U <
18
AM1 level 0/4-20mA >
19
AM1 level 0/4-20mA <
20
Stalled rotor
21
No start possible
22 Number of starts >
23
Just one start possible
24 Motor operating hours >
25
Motor stop time >
26
External fault 1
27
External fault 2
28
External fault 3
29
External fault 4
30
External fault 5
31
External fault 6

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals