3RT1/3RH1 contactors
SIRIUS System Manual
GWA 4NEB 430 0999-02b
3-11
The following table provides an overview of the existing variants of the 3RT and 3RH contactors:
Table 3-7: Types of 3RT/3RH contactors
Models Frame size
3RT10 contactors AC/DC operation
To operate motors, 3-pole, up to 45 kW/400 V
I
e
/AC-1 up to 40 °C: up to 120 A to 690 V
I
e
/AC-3 up to 60 °C: up to 95 A/400 V
S00 to S3
3RT14 contactors AC/DC operation
To switch resistive loads, 3-pole, up to 92 kW/400 V
I
e
/AC-1 at 40 °C: up to 140 A to 690 V
S3
3RT13 contactors AC/DC operation, 4 main contacts (NO contacts)
To switch resistive loads, up to 92 kW/400 V
I
e
/AC-1 up to 40 °C: up to 140 A to 690 V
S00 to S3
3RT15 contactors AC/DC operation, 4 main contacts (2 NO contacts + 2 NC contacts)
To switch three-phase induction motors up to 18.5 kW/400 V
I
e
/AC-3 up to 60 °C: up to 40 A to 400 V
S00 to S2
3RT16 contactors AC operation
To switch three-phase capacitors up to 50 kvar/400 V
S0 to S3
3RH/3RT contactors DC operation with an extended operating range: 0.7 to 1.25 x U
S
3RT: to switch motors up to 45 kW/400 V
I
e
/AC-3 up to °C: 95 A to 400 V
3RH: to switch auxiliary circuits
I
e
/AC-15/AC-14 up to 70 °C: 6 A/230 V
S00 to S3
3RT contactor relays
(interface)
DC operation with an extended operating range: 0.7 to 1.25 x U
S
To switch motors, 3-pole, up to 11 kW/400 V
I
e
/AC-3 up to 60 °C: 25 A to 400 V
S00 and S0
3RA13 contactor combina-
tions
AC/DC operation
To reverse up to 45 kW/400 V, I
e
/AC-3: 95 A/400 V
S00 to S3
3RA14 contactor combina-
tions
AC/DC operation,
for star-delta startup up to 75 kW/400 V, I
e
/AC-3: 150 A/400 V
S00-S00-S00 to
S3-S3-S2
3RH11 auxiliary contactors AC/DC operation,
to switch auxiliary circuits, 4-pole (basic unit)
I
e
/AC-15/AC-14 up to 60 °C: 6 A/230 V
S00
3RH14 latched auxiliary
contactors
AC/DC operation,
to switch auxiliary circuits, 4-pole (basic unit)
I
e
/AC-15/AC-14 up to 60 °C: 6 A/230 V
S00
3RH11 contactor relays
(interface)
DC operation with an extended operating range (0.7 to 1.25 x U
S)
to switch auxiliary circuits, 4-pole
I
e
/AC-15/AC-14 up to 60 °C: 6 A/230 V
S00
Unwelded contactors
3RT11 24, 3RT11 35
The unwelded contactors are put together using a circuit breaker to
make an unwelded feeder. The features are:
Standard: IEC 947-6-2 (for feeders with increased requirements)
•Compact
Extremely high reliability in the entire current range up to 50 kA
S0, S2

Table of Contents

Other manuals for Siemens SIRIUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS and is the answer not in the manual?

Siemens SIRIUS Specifications

General IconGeneral
BrandSiemens
ModelSIRIUS
CategoryRelays
LanguageEnglish

Related product manuals