3RW3 semiconductor motor control unit
SIRIUS System Manual
GWA 4NEB 430 0999-02b
8-49
Fused configuration
The following table specifies the components of the fused configuration
(coordination type 1) for 3RW30/31; short-circuit current of 50 kA/400 V:
Table 8-21: Motor feeder: fused configuration
1) The selection and setting of the overload relay is based on the rated cur-
rent for the motor
2) Short-circuit current of 50 kA to max. 400 V
3) Short-circuit current of 50 kA to max. 500 V
4) 50 mm clearance is required above and below between the 3RW and
grounded parts
Order number
of the soft
starter
Order
number
of the fuse
Fuse rated
current/
frame size
Order number
of the therm.
overload
relay
1)
Order
number
of the elec-
tron. over-
load relay
1)
Order
number
of the
contactor
MLFB MLFB A / size MLFB MLFB MLFB
3RW3014 3NA3810 25 / 00 3RU1116
2)4)
3RB1016
2)4)
3RT1015
3RW3016 3NA3810 25 / 00 3RU1116
2)4)
3RB1016
2)4)
3RT1016
3RW3024/
3RW3124
3NA3822 63 / 00 3RU1126
3)
3RB1026
3)
3RT1024
3RW3025/
3RW3125
3NA3822 63 / 00 3RU1126
3)
3RB1026
3)
3RT1025
3RW3026/
3RW3126
3NA3824 80 / 00 3RU1126
3)
3RB1026
3)
3RT1026
3RW3034 3NA3830 100 / 00 3RU1136
3)
3RT1034
3RW3035 3NA3830 100 / 00 3RU1136
3)
3RT1035
3RW3036 3NA3830 100 / 00 3RU1136
3)
3RT1036
3RW3044 3NA3144 250 / 1 3RU1146
3)
3RT1044
3RW3045 3NA3144 250 / 1 3RU1146
3)
3RT1045
3RW3046 3NA3144 250 / 1 3RU1146
3)
3RT1046