1) = SIRIUS 3RW301 .. soft starters cannot be used with a fan
Without fan
Stand-alone installation
Without fan
Installed side by side
With fan
Stand-alone installation
With fan
Installed side by side
Order number
Frame size
Device rated current in A
at an ambient temperature of 40 °C
Order number
Circuit breaker
Adjustment range
Circuit breaker
Correction factor
Rated current for the device
Correction factor
Switching frequency
Correction factor
Current setting of the circuit breaker
Correction factor
Rated current for the device
Correction factor
Switching frequency
Correction factor
Current setting of the circuit breaker
Correction factor
Rated current for the device
Correction factor
Switching frequency
Correction factor
Current setting of the circuit breaker
Correction factor
Rated current for the device
Correction factor
Switching frequency
Correction factor
Current setting of the circuit breaker
3RW3014-1CB..
3RW3016-1CB..
S00
S00
6
9
3RV1011-1GA10
3RV1011-1JA10
(4.5 - 6.3) A
(7 - 10) A
1
1
0.9
0.9
1
1
1
1
0.5
0.5
1.
1.
-
1)
-
1)
-
1)
-
1)
-
1)
-
1)
-
1)
-
1)
-
1)
-
1)
-
1)
-
1)
3RW3.24-1AB..
3RW3.25-1AB..
3RW3.26-1AB..
S0
S0
S0
12.
16
25
3RV1021-1KA10
3RV1021-4AA10
3RV1021-4DA10
(9 - 12.) A
(11 - 16) A
(20 - 25) A
1
1
1
0.5
0.5
0.75
1
1
1
1
1
0.
0.5
0.5
0.5
1.
1.
1.
1
1
1
1.
1.
1.
1
1
1
1
1
1
1. 7
1. 7
1. 7
1. 1
1. 1
1. 1
3RW3034-1AB..
3RW3035-1AB..
3RW3036-1AB..
S2
S2
S2
32
38
45
3RV1031-4EA10
3RV1031-4FA10
3RV1031-4GA10
(22 - 32) A
(28 - 40) A
(36 - 45) A
1
1
1
0.65
0.85
0.85
1
1
1
0.9
0.95
0.9
0.45
0.35
0.4
1. 1
1. 1
1. 1
1
1
1
2.2
1. 8
1. 8
1
1
1
1
1
1
1. 9
1. 7
1. 7
1. 1
1. 1
1. 1
3RW3044-1AB..
3RW3045-1AB..
3RW3046-1AB..
S3
S3
S3
63
75
100
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4MA10
(45 - 63) A
(57 - 75) A
(80 - 100) A
1
1
1
0.85
0.8
0.75
1
1
1
0.95
0.9
0.85
0.6
0.5
0.55
1. 1
1. 1
1. 1
1
1
1
1. 6
1. 6
1. 6
1
1
1
1
1
1
1. 3
1. 3
1. 2
1. 1
1. 1
1. 1