9.2.3.3 Lower level point (2.3.3)
Sets level value when material is at lower calibration point.
Setting -99999 to 99999 m
Default 0.0 m
9.2.3.4 Upper level point (2.3.4)
Se
ts level value when material is at upper calibration point.
Setting -99999 to 99999 m
Default 30 m
9.2.3.5 Sensor o󹪜se
t (2.3.5)
Sets o󹪜set to compensate for changes in sensor reference point.
Changes to sensor reference point may result from adding a thicker gasket or reducing the
stando󹪜/nozzle height.
Setting -99.999 to 99.999 m
Default 0
If amount of parameter "Sensor o󹪜set" is known, enter the constant that can be added to or
subtracted from sensor value
1)
to compensate if the sensor reference point has shifted.
1)
The value produced by the echo processing which represents the distance from sensor
reference point to the target
9.2.3.6 Low-level cuto󹪜 (2.3.6)
Sets lower limit on measured value (before any o󹪜set applied).
For example, set value to zero to prevent a negative level measurement.
Setting -999 to 0.0
Default 0.0
Note
Def
ault value disables parameter
By using the default value of -999, or a lower value, the parameter "Low-level cuto󹪜" is disabled.
9.2.3.7 Propagation factor (2.3.7)
Se
ts value that represents reduction in propagation velocity as a result of the wave travelling
through a pipe.
Parameter assignment
9.2î™ Setup (2)
SITRANS LR500 series with mA/HART
Operating Instructions, 03/2024, A5E51099898-AA 119

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITRANS LR580 and is the answer not in the manual?

Siemens SITRANS LR580 Specifications

General IconGeneral
BrandSiemens
ModelSITRANS LR580
CategoryTransmitter
LanguageEnglish

Related product manuals