Setting 0.3 to 1.1
Default 1.0
9.2.3.8 Antenna ose
t (2.3.8)
Sets oset required if electronics module is replaced. Consult your local Siemens representative
for support.
Setting -0.2 to 0.2 m
Default 0.0 m
9.2.4 Current output (2.4)
9.2.4.1
Loop current mode (2.4.1)
Sets operation of Loop current for HART multidrop mode.
Setting Enabled
Disabled
Default Enabled
The device is in loop current mode by default. Disabling parameter "Loop current mode"
will r
esult in a xed loop current setting for multidrop operation (see Loop current value in
multidrop mode (2.4.2) (Page120)).
9.2.4.2 Loop current value in multidrop mode (2.4.2)
Sets mA value for loop current in HART multidrop mode.
Setting 3.6 to 22.8 mA
Default 4 mA
9.2.4.3 Damping value (2.4.3)
Se
ts the damping (ltering) of the PV to smooth out response to sudden changes in
measurement.
An increase of damping increases response time of device, and aects digital value and loop
current. If output values are noisy, increase parameter "Damping value". For faster response
time, decrease parameter "Damping value". Find a value that meets requirements of signal
stability and response time.
Setting 0 to 1500 s
Default 10 s
Parameter assignment
9.2Setup (2)
SITRANS LR500 series with mA/HART
120 Operating Instructions, 03/2024, A5E51099898-AA