Setting Disabled
Enabled
Ramp
Default Disabled
Set to "Enabled" to hold the simulation at a specic v
alue. Set to "Ramp" to have the
simulation continuously sweep through the measurement range.
9.3.7.2 Simulation value (3.7.2)
Sets starting value for ramp or xed simulation.
Setting Not limited
Default Not applicable
9.3.7.3 PV status (3.7.3)
Se
ts status of the PV to simulate.
Setting Good
Bad
Uncertain
Default Good
9.3.7.4 Ramp end (3.7.4)
Se
ts end value for ramp simulation.
Setting Not limited
Default Not applicable
9.3.7.5 Ramp steps (3.7.5)
Se
ts number of stair steps between ramp start (parameter "Simulation value") and end of ramp
simulation.
Setting 0 to 65535
Default 10
9.3.7.6 Ramp duration (3.7.6.)
Sets total time from ramp start (parameter "Simulation value") to end of ramp simulation.
Setting 0 to 65535
Default 5
Parameter assignment
9.3Maintenance and diagnostics (3)
SITRANS LR500 series with mA/HART
142 Operating Instructions, 03/2024, A5E51099898-AA