EasyManuals Logo
Home>GE>Control Unit>P24DM

GE P24DM User Manual

GE P24DM
802 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #443 background imageLoading...
Page #443 background image
E00800
IED
S F
V
RES
=
Z
S0
2Z
S1
+ Z
S0
+ 2Z
L1
+ Z
L0
X 3 E
E
Z
S
Z
L
V
A
V
A
V
A
V
A
V
C
V
C
V
C
V
C
V
C
V
C
V
B
V
B
V
B
V
B
V
B
V
B
V
RES
V
RES
Figure 235: Residual voltage for a solidly earthed system
As can be seen from the above diagram, the residual voltage measured on a solidly earthed system is solely
dependent on the ratio of source impedance behind the protection to the line impedance in front of the protection,
up to the point of fault. For a remote fault far away, the Z
S
/Z
L
: ratio will be small, resulting in a correspondingly
small residual voltage. Therefore, the protection only operates for faults up to a certain distance along the system.
The maximum distance depends on the device setting.
5.3.2
CALCULATION FOR IMPEDANCE EARTHED SYSTEMS
Consider a Phase-A to Earth fault on a simple radial system.
P543i/P545i Chapter 14 - Voltage Protection Functions
P54x1i-TM-EN-1 407

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P24DM and is the answer not in the manual?

GE P24DM Specifications

General IconGeneral
BrandGE
ModelP24DM
CategoryControl Unit
LanguageEnglish

Related product manuals