EasyManuals Logo

Juniper MX10008 User Manual

Juniper MX10008
361 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #181 background imageLoading...
Page #181 background image
SEE ALSO
Installing an MX10008 Fan Tray | 183
MX10008 Cooling System and Airflow | 45
Field-Replaceable Units in an MX10008 | 38
Installing an MX10008 Fan Tray
An MX10008 chassis has two independent, field-replaceable fan trays. Each fan tray is a hot-removable
and hot-insertable field-replaceable unit (FRU); you can remove and replace the fan tray while the router
is running without turning off power to the router or disrupting routing functions. There are two models
of the fan tray, JNP10008-FAN and JNP10008-FAN2.
Each fan tray is installed vertically on the rear, or FRU-side, of the chassis.
Before you begin to install a fan tray:
Ensure you understand how to prevent ESD damage. See “Prevention of Electrostatic Discharge Damage”
on page 343.
Ensure that you have the following parts and tools available to install a fan tray:
Electrostatic discharge (ESD) grounding strap
A Phillips (+) screwdriver, number 1 or 2 (optional), for the captive screws
A replacement fan tray
CAUTION: The fan tray can be removed and replaced while the router is operating. Fan
trays must be replaced within the duration mentioned in Table 56 on page 179.
183

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper MX10008 and is the answer not in the manual?

Juniper MX10008 Specifications

General IconGeneral
BrandJuniper
ModelMX10008
CategoryNetwork Router
LanguageEnglish

Related product manuals