7 Wiring
7 - 8
NX-series EtherCAT Coupler Unit User’s Manual (W519)
7-2 Connecting the Power Supply and
Ground Wires
This section describes how to wire the power supplies and ground the EtherCAT Slave Terminal.
The wiring of the power supply and ground to the EtherCAT Coupler Unit is shown in the following fig-
ure.
Unit Power Supply Terminals
These terminals are connected to the Unit power supply. The details are given in the following table.
You can use the unwired terminals for through-wiring to an Additional NX Unit Power Supply Unit or
to the Unit power supply terminals on another EtherCAT Coupler Unit. Make the current supplied
from the unwired terminals meet the following conditions.
Current supplied from unwired terminals = Current capacity of power supply terminals − Current
consumption of the EtherCAT Coupler Unit block
Refer to 5-4-1 Selecting the Unit Power Supply on page 5-15 for details on blocks.
I/O Power Supply Terminals
These terminals are connected to the I/O power supply. The details are given in the following table.
Provide a power supply voltage that is within the power supply voltage specifications of the NX Unit
I/O circuits and connected external devices.
7-2-1 Wiring the EtherCAT Coupler Unit
Terminal number
indication
Terminal name Description
A1 or B1 UV Connect the 24-VDC wire (positive side) from the Unit power
supply to either the A1 or B1 terminal.
A3 or B3 UG Connect the 0-VDC wire (negative side) from the Unit power
supply to either the A3 or B3 terminal.
Terminal number
indication
Terminal name Description
A5 IOV Connect the 5 to 24-VDC wire (positive side) from the I/O
power supply.
B5 IOG Connect the 0-VDC wire (negative side) from the I/O power
supply.
I/O power supply
(5 to 24 VDC)
Ground to
100 Ω or less
Through-wiring for unwired
terminals
IOV
UG
UV
IOG
UV
UG
A1
A8
B1
B8
Unit power
supply