5-4
5
îš‹ User Parameters Available in Quick Programming Mode
The minimum user parameters required for Inverter operation can be monitored and set in quick programming
mode. The user parameters displayed in quick programming mode are listed in the following table. These, and
all other user parameters, are also displayed in advanced programming mode.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
A1-02
Control
method
selection
Sets the control method for the Inverter.
0: V/f control
1: V/f control with PG
2: Open Loop Vector control
3: Closed Loop Vector control
0 to 30 NoQQQQ102H
Control
Method
b1-01
Reference
source selec-
tion
Sets the frequency reference input
method.
0: Digital Operator
1: Control circuit terminal (analog
input)
2: MEMOBUS communications
3: Option Card
4: Pulse train input
0 to 41 NoQQQQ180H
Reference
Source
b1-02
RUN source
selection
Sets the run command input method
0: Digital Operator
1: Control circuit terminal (digital multi
function inputs)
2: MEMOBUS communications
3: Option Card
0 to 31 NoQQQQ181H
Run Source
b1-03
Stopping
method
selection
Select stopping method when stop com-
mand is input.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop (Stops faster than
coast to stop, without regenerative
operation.)
3: Coast to stop with timer (Run
commands are disregarded during
deceleration time.)
0 to 30 NoQQQQ182H
Stopping
Method
C1-01
Accelera-
tion time 1
Sets the acceleration time to accelerate
from 0 Hz to the maximum output fre-
quency.
0.0 to
6000.0
* 1
10.0
sec
YesQQQQ
200H
Accel
Time 1
C1-02
Decelera-
tion time 1
Sets the deceleration time to decelerate
from the maximum output frequency to
0 Hz.
201H
Decel
Time 1
C6-01
Heavy/Nor-
mal Duty
selection
0: Heavy Duty
1: Normal Duty 1
2: Normal Duty 2
0 or 2 0 No Q Q Q Q 223H
Heavy/Nor-
mal Duty
C6-02
Carrier fre-
quency
selection
Selects the carrier frequency.
Select F to enable detailed settings using
parameters C6-03 to C6-05.
0 to F1 NoQQQQ224H
Carrier Freq
Sel

Table of Contents

Other manuals for Omron VARISPEED F7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron VARISPEED F7 and is the answer not in the manual?

Omron VARISPEED F7 Specifications

General IconGeneral
BrandOmron
ModelVARISPEED F7
CategoryInverter
LanguageEnglish

Related product manuals