6-62
6
îš‹ Operation Selection After Cooling Fan Fault
Use the parameter setting to select the operation of the motor after a cooling fan fault occurs. This function can
be used for times when a motor should not be stopped quickly (with an emergency stop.)
Related Parameters
The following table describes the operation of the motor and the display of the Digital Operator in accordance
with the settings of the L8-32 if a cooling fan fault occurred.
Parameter
No.
Name
Factory
Setting
Change
during
Opera-
tion
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Closed
Loop
Vector
L8-32 OH1 detection of Inverter’s cooling fan 1 No A A A A
Setting
value
Fault Digital Operator Motor Operation
Multi-function Digital
Output
0
Cooling Fin Overheat OH1 Coast to stop Fault
Inverter’s Cooling Fin FAN (flashing)
Continue operation
* 1
* 1. If l8-32 is set to 0, the motor will continue running even if a cooling fan fault occurred. However, the Inverter rated output current and the
overload capacity will be reduced. The rated output current will be reduced to 80% of the Inverter rated current and the overload capacity
will be reduced to following values:
When CT (C6-01=0, default) is selected: 100% for 3 minutes, 150% for 15 seconds.
When VT (C6-01=1 or 2) is selected: 100% for 30 seconds, 120% for 10 seconds.
Alarm
1
Cooling Fin Overheat OH Coast to stop Fault
Inverter’s Cooling Fin OH1 Coast to stop Fault
IMPORTANT
If L8-32 is set to 0, be sure to set H2-01 to H2-03 multi-function digital outputs to 10 (Alarm)
or to 3D (Inverter’s cooling fan fault.) If a cooling fan fault occurs, stop the Inverter immedi-
ately and replace the cooling fan. If the Inverter continues to run while a cooling fan fault
occurs, the Inverter’s cooling ability will be affected and the Inverter’s internal temperature
will increase and shorten the Inverter’s life time. During a cooling fan fault, the cooling fan
stops for about 3 seconds every minute (interval operation.)