4-6
4
* The setting range is valid if Heavy Duty is selected (C6-01=0, default setting). If Normal Duty 1 or 2 is selected (C6-01=1 or 2) the setting range will be
0.0 to 400.0 Hz.
E1-01
Input voltage set-
ting
Sets the Inverter's nominal input voltage
in volts.
155 to 255 V
(200 V class)
310 to 510 V
(400 V class)
200 V
(200 V
class)
400 V
(400 V
class)
5-31
6-113
E2-01
Motor rated cur-
rent
Sets the motor rated current.
10% to 200%
of Inverter's
rated current
Setting for
general-
purpose
motor of
same
capacity as
Inverter
5-32
6-51
6-111
H4-02
and
H4-05
FM and AM ter-
minal output gain
Can be used to adjust the analog output
when an instrument is connected to the
FM or AM terminal.
0.0 to
1000.0%
H4-02:
100%
H4-05:
50%
5-49
L1-01
Motor protection
selection
Used to enable or disable the motor over-
load protection function.
0: Disabled
1: Protection for general purpose motor
(fan cooled)
2: Protection for frequency converter
motor (externally cooled)
3: Protection for special vector control
motor
0 to 3 1
5-52
6-51
L3-04
Stall prevention
selection during
deceleration
If using the dynamic brake option (brak-
ing resistor, Braking Resistor Units and
Braking Units), be sure to set parameter
L3-04 to 0 (disabled) or 3 (enabled with
braking resistor).
0 to 3 1
5-55
6-25
Table 4.1 Basic Parameter Settings (Continued)
: Must be set. : Set as required.
Class
Parame-
ter Num-
ber
Name Description
Setting
Range
Factory
Setting
Page