Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
169
BatteryConnection
Boolean PropertyType The connection to the battery has been interrupted or has a
BatteryCount Byte PropertyType Number of connected batteries. Only coded batteries are
counted.
BufferMode Enumeration MultiState
Indicates buffer mode
Sufficient buffer readiness
BufferRemainingTime UInt32 AnalogItemType Estimated remaining buffer time. The remaining buffer time
is calculated using the current battery charge level and
average current over 10 minutes.
ChargeMeasured
Float AnalogItemType Measured battery charge current
ChargeSufficient Boolean PropertyType When this flag is set, the required charge level has been
DeviceAlarmLed Object Sitop_1600_
Status of LED "Alarm"
DeviceBatteryFaultLed Object Sitop_1600_
Status of LED "BatteryFault"
DeviceBattery
Object Sitop_1600_
Status of LED "BatteryOver85"
DeviceCalculated
Float AnalogItemType Available battery capacity
DeviceCalculated
Byte AnalogItemType State of health (SoS) as percentage of the rated capacity
Measured input current of SITOP UPS1600
DeviceInputVoltage Float AnalogItemType Input voltage
DeviceInputVoltageOK Boolean PropertyType Input voltage has exceeded the configured threshold volt-
age. Connected devices are powered with the input supply.
Measured output current of SITOP UPS1600