Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
169
Display name
Data type
Definition
Description
BatteryConnection
Fault
Boolean PropertyType The connection to the battery has been interrupted or has a
high impedance.
BatteryCount Byte PropertyType Number of connected batteries. Only coded batteries are
counted.
BatteryVoltage
Float
AnalogItemType
Current battery voltage
3.8.6.3
ActualBufferState
Display name
Data type
Definition
Description
BufferMode Enumeration MultiState
DiscreteType
Indicates buffer mode
BufferReady
Boolean
PropertyType
Sufficient buffer readiness
BufferRemainingTime UInt32 AnalogItemType Estimated remaining buffer time. The remaining buffer time
is calculated using the current battery charge level and
average current over 10 minutes.
3.8.6.4
ActualChargingState
Display name
Data type
Definition
Description
ChargeMeasured
Current
Float AnalogItemType Measured battery charge current
ChargeSufficient Boolean PropertyType When this flag is set, the required charge level has been
achieved
3.8.6.5
ActualState
Display name
Data type
Definition
Description
DeviceAlarmLed Object Sitop_1600_
LedType
Status of LED "Alarm"
DeviceBatteryFaultLed Object Sitop_1600_
LedType
Status of LED "BatteryFault"
DeviceBattery
Over85Led
Object Sitop_1600_
LedType
Status of LED "BatteryOver85"
DeviceCalculated
Capacity
Float AnalogItemType Available battery capacity
DeviceCalculated
Health
Byte AnalogItemType State of health (SoS) as percentage of the rated capacity
DeviceInputCurrent
Float
AnalogItemType
Measured input current of SITOP UPS1600
DeviceInputVoltage Float AnalogItemType Input voltage
DeviceInputVoltageOK Boolean PropertyType Input voltage has exceeded the configured threshold volt-
age. Connected devices are powered with the input supply.
DeviceLoadCurrent
Float
AnalogItemType
Measured output current of SITOP UPS1600

Table of Contents

Other manuals for Siemens 6EP4134-3AB00-2AY0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6EP4134-3AB00-2AY0 and is the answer not in the manual?

Siemens 6EP4134-3AB00-2AY0 Specifications

General IconGeneral
BrandSiemens
Model6EP4134-3AB00-2AY0
CategoryPower Supply
LanguageEnglish

Related product manuals