Page #179 background imageLoading...
Page #179 background image
Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
179
Display name
Data type
Definition
Description
AlarmBattery
TemperatureLow
Boolean PropertyType Battery temperature too low - reduced output current
AlarmFuseBroken Boolean PropertyType Fuse is defective.
AlarmNewBattery
Detected
Boolean PropertyType A new battery was connected. The battery will be included
in the calculation of the total capacity and the charge pa-
rameters.
BufferTime
UInt32
AnalogItemType
Desired buffering time before device switches off
BufferingEndVoltage Float AnalogItemType When battery voltage is lower than this voltage, the battery
charge is no longer sufficient. Buffering is stopped.
ChargeCurrent
Float
AnalogItemType
Actual charging current used to charge battery.
ChargeEndVoltage Float AnalogItemType Battery voltage when charging changes to trickle charging.
Battery is charged 100%.
ChargeTotalCurrent Float AnalogItemType Battery-specific data: Total charge to the battery during its
service life
ModuleCalculated
Capacity
Float AnalogItemType Available battery capacity
ModuleCalculated
Health
Byte AnalogItemType State of health (SoS) as percentage of the rated capacity
ModuleCapacity
Float
AnalogItemType
Capacity
ModuleChange
Recommended
Boolean PropertyType Battery cap
acity is insufficient to achieve the specified buffer
time.
ModuleCompound Enumeration MultiState
DiscreteType
Connected device
ModuleConnection
Fault
Boolean PropertyType Connection to battery interrupted - check connection and
fuse
ModuleMax
Temperature
Sbyte AnalogItemType Maximum specified operating temperature of the battery.
ModuleMin
Temperature
Sbyte AnalogItemType Minimum specified operating temperature of the battery.
ModuleStandbyTime UInt32 AnalogItemType Battery-specific data: Time for which battery was connected
but no power was consumed.
ModuleStateLed Object Sitop_1600_
LedType
ModuleStateLed
ModuleTemperature
Sbyte
AnalogItemType
Battery temperature
ModuleTotal
CulledCurrent
Float AnalogItemType Battery-specific data: Time for which battery was connected
and power was consumed.
3.8.6.22
UserManagement
Display name
Data type
Definition
Description
AddUser
Method
Method
Adds a user.
ChangeUserPassword
Method
Method
Changes the password for the user.
DeleteUser
Method
Method
Deletes the user.
UsermanagementUser
1 … 16
SitopUserType SitopUserType

Table of Contents

Other manuals for Siemens 6EP4134-3AB00-2AY0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6EP4134-3AB00-2AY0 and is the answer not in the manual?

Siemens 6EP4134-3AB00-2AY0 Specifications

General IconGeneral
BrandSiemens
Model6EP4134-3AB00-2AY0
CategoryPower Supply
LanguageEnglish

Related product manuals