Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
179
AlarmBattery
Boolean PropertyType Battery temperature too low - reduced output current
AlarmFuseBroken Boolean PropertyType Fuse is defective.
AlarmNewBattery
Detected
Boolean PropertyType A new battery was connected. The battery will be included
in the calculation of the total capacity and the charge pa-
Desired buffering time before device switches off
BufferingEndVoltage Float AnalogItemType When battery voltage is lower than this voltage, the battery
charge is no longer sufficient. Buffering is stopped.
Actual charging current used to charge battery.
ChargeEndVoltage Float AnalogItemType Battery voltage when charging changes to trickle charging.
ChargeTotalCurrent Float AnalogItemType Battery-specific data: Total charge to the battery during its
ModuleCalculated
Float AnalogItemType Available battery capacity
ModuleCalculated
Byte AnalogItemType State of health (SoS) as percentage of the rated capacity
ModuleChange
Boolean PropertyType Battery cap
acity is insufficient to achieve the specified buffer
time.
ModuleCompound Enumeration MultiState
DiscreteType
Connected device
ModuleConnection
Boolean PropertyType Connection to battery interrupted - check connection and
ModuleMax
Sbyte AnalogItemType Maximum specified operating temperature of the battery.
ModuleMin
Sbyte AnalogItemType Minimum specified operating temperature of the battery.
ModuleStandbyTime UInt32 AnalogItemType Battery-specific data: Time for which battery was connected
but no power was consumed.
ModuleStateLed Object Sitop_1600_
ModuleStateLed
ModuleTotal
Float AnalogItemType Battery-specific data: Time for which battery was connected
Changes the password for the user.
UsermanagementUser
SitopUserType SitopUserType