Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
170 Manual, 04.2017, A5E37775406-8-76
Maximum output current supported by the SITOP UPS1600
DeviceOutputCurrent Float AnalogItemType Measured output current of SITOP UPS1600
DeviceP1LinkLed Object Sitop_1600_
LedType
Status of LED "P1"
DeviceP2LinkLed Object Sitop_1600_
Status of LED "P2"
DeviceRunLed Object Sitop_1600_
Status of LED "RUN"
DeviceSFLed Object Sitop_1600_
Status of LED "SF"
DeviceSWSettings
Valid
Boolean PropertyType This object provides information about whether the SW
parameters or the parameters at the rotary switches are
used. The desired setting is selected on rotating switch for
DeviceStateLed Object Sitop_1600_
Status of LED "OK": Device status
DeviceTotalOperating
UInt32 AnalogItemType Battery-specific data: Total time for which battery was in
buffer mode during its service life
UpdateState Enumeration MultiState
Update status
AlarmBattery
Boolean PropertyType Connection to battery interrupted - check connection and
AlarmBattery
ConnectionHigh
Boolean PropertyType High-resistance connection to battery - check battery power
cable
AlarmBatteryDeep
Boolean PropertyType Battery is deep discharged - no buffering possible
AlarmBatteryDeep
DischargeNoCharging
Boolean PropertyType Battery is deep discharged - replace battery
Battery defective - check fuse and battery voltages
Battery 'state of health' (SOH) tests are in progress