Engineering and remote access
3.3 SIMATIC STEP 7 in the TIA Portal
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
69
3.3.10
Firmware update
WARNING
The SITOP UPS1600 is reset while updating the firmware. For safety reasons, the output is
switched off.
Ensure that no damage is caused to the plant or system.
Ensure that the PG/PC and/or all switches, routers and gateways that are used have an
independent power supply during the firmware update.
WARNING
Firmware update with UPS-Manager
If for the firmware update, the UPS Manager is used, please note that for a firmware update
from version V2.1 to V2.2 or higher, then a UPS Manager with version V4.72 or higher must
be used. This also applies to firmware updates from V2.2.0 to higher versions.
Note
Install the current version of the SITOP UPS Managers, before you start the firmware
update. It is possible that an older version (less than V4.5X) of the SITOP UPS Managers
does not support this firmware update. T
he installation file for the SITOP UPS Manager is
available at no charge on the SITOP home page (
http://www.siemens.com/sitop) or directly
(
https://support.industry.siemens.com/cs/ww/en/view/75854607).
Note
Do not switch
-off the devices during the firmware update.
The files for updating the firmware (firmware updates) are available online under
(http://support.automation.siemens.com/WW/view/en/79207181
). Different firmware updates
are offered depending on the amp rating of the SITOP UPS1600.
Note
Observe the compatibility of the firmware!
Other fir
mware updates are not compatible.
Determine the amp rating of your SITOP
UPS1600 and download the appropriate firmware
update.
Note
It is not possible to downgrade the device firmware to a release with a version number lower
than the firmware installed
in the device itself. Information on how to read out the firmware
release from the device is provided in Section
Diagnostics (Page 67).

Table of Contents

Other manuals for Siemens 6EP4134-3AB00-2AY0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 6EP4134-3AB00-2AY0 and is the answer not in the manual?

Siemens 6EP4134-3AB00-2AY0 Specifications

General IconGeneral
BrandSiemens
Model6EP4134-3AB00-2AY0
CategoryPower Supply
LanguageEnglish

Related product manuals