SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
203
Note
When installing the devices, the relevant country
-specific regulations must be complied with.
V supply voltage must be SELV in accordance with EN60950-1 and EN50178.
Only qualified personnel are allowed to install the device/system and set it into operation.
It is not permissible that the connections are attached or
detached in operation.
Note
for SITOP UPS1100
It is recommended that the batteries are only stored fully charged.
The lead acid batteries are fully charged when the device is delivered. The LiFePo battery
(5
Ah) is only supplied charged up to a maximum of 30 % of the nominal charge (to comply
with transport regulations).
-discharge rate of the batteries is approx. 3%/month for a temperature of 20°
C. This
value is temperature dependent and becomes more unfavorable for an increasing
temperature
, and more favorable for a decreasing temperature.
The fuses should only be inserted in the fuse holder when commissioning the device.
When storing UPS1100 battery modules and completely cabled/wired systems (with
UPS1600 and fuse inserted in the UPS1100),
it should be taken into account that an
additional discharge current of 300
µA flows.
UPS1100 1.2 Ah is only recommended in conjunction with SITOP UPS1600 10 A.
UPS1100 2.5 Ah, 3.2 Ah and 5 Ah are only recommended in conjunction with
UPS1600 10 A and 20 A.
When using battery modules without Energy Storage Link, it must be ensured that the
selected batteries match the data of the UPS1600 (static and dynamic load current, charge
current).