Parameter
A.1 MMDiag block parameter
SIMOCODE pro PCS 7 Library V9.0
236 Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
Parameter
Data format
Default setting
Meaning
PA_Diag
DWORD
16#00
Diagnostic information for maintenance
Slv_Typ BOOL FALSE 0 = PROFIBUS
1 = PROFINET
Diag_Sts SMCSTATUS
(Page 237)
SIMOCODE diagnostic status information
Diag_Evt SMCEVNT
(Page 238)
SIMOCODE diagnostic event information
Diag_Wrn SMCWRNG
(Page 240)
SIMOCODE diagnostic warning information
Diag_Trp SMCTRP
(Page 242)
SIMOCODE diagnostic trip information
ST_Worst
BYTE
16#80
Worst Signal Status
OMode
DWORD
16#00
Status MODE
ErrorNum
INT
-1
Error number
MsgErr1
BOOL
FALSE
1 = Messaging error occurs
MsgStat1
WORD
16#00
ALARM_8P: Status Output
MsgAckn1
WORD
16#00
ALARM_8P: ACK_STATE Output
ReserveOut
WORD
16#00
Reserved
Structure of OMODE
Table A- 3 Structure of OMODE – MMDiag
Byte
Value
Meaning
Byte 3 16#80:
16#40:
16#20:
Valid data
Invalid data
Redundancy error
Irrelevant
Byte 2
16#01:
Warm restart (OB100)
–
Byte 1; 0
16#0000
–
Irrelevant

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals