SIRIUS 3RF34 solid-state switching devices
3.2 Product description
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
319
3.2.3 Application environment
General operating conditions
The following table lists the general operating conditions under which the product may be
operated.
Table 3- 3 General operating conditions
Operating conditions Value
Degree of protection IP20
Ambient temperature during operation - 25 to 60 °C
Installation altitude 0 to 1000 m;
at > 1,000 m seek advice from Technical Assistance
(www.siemens.com/lowvoltage/technical-assistance
)
Shock resistance 15 g/11 ms; acc. to DIN IEC 68-2-27
Vibration resistance 2 g; acc. to DIN IEC 68-2-6
EMC conditions Acc. to DIN IEC 60947-4-2, DIN IEC 61000-4-2,
DIN IEC 61000-4-4, DIN IEC 61000-4-5, and
DIN IEC 61000-4-6,
Insulation strength 50/60 Hz 4,000 V
rms
Reference
More information ... Can be found in the chapter titled
About operating conditions for solid-state
switching devices
Technical data (Page 350)