SIRIUS 3RR2 current monitoring relays
8.8 Operation
SIRIUS Innovations
708 System Manual, 01/2011, A8E56203870002-03
8.8.1.5 Tripping delay time
Definition of tripping delay time (Del)
The set tripping delay time starts when the monitoring current overshoots or undershoots the
corresponding set threshold value.
Explanation
The set tripping delay time starts when the load current flowing under normal operating
conditions overshoots or undershoots the corresponding set threshold value. The red FAULT
LED flashes. Once this time has elapsed, the switching contact changes the switching state
and the FAULT LED lights up continuously if the current value is still outside the correct
range. As a result, transient current oscillations are ignored and do not lead to undesirable
switching operations (alarms, for example).
Note
Special cases wire break/phase failure
A delay time is not observed if a wire break or phase failure is detected. The current
monitoring relay responds immediately (≤ 300 ms) in such cases.
Setting range
The setting range for the tripping delay is continuously 0 s to 30 s.
Factory setting
The tripping delay is factory-set to 0 s.
Changes to settings
Changes to the tripping delay time can be made by adjusting the corresponding rotary button
(Del) with a screwdriver.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS 3RF Series and is the answer not in the manual?

Siemens SIRIUS 3RF Series Specifications

General IconGeneral
BrandSiemens
ModelSIRIUS 3RF Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals