SIRIUS 3RR2 current monitoring relays
8.10 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
741
8.10.2.3 Connection for main circuit
Table 8- 20 Technical data for the main circuit connection, 3RR21 current monitoring relays
Type 3RR2141 3RR2142
Size S00 S0
Width 45 mm 45 mm
Connection type Screw connection
ï‚· Connection screw
M3, Pozidriv size 2 M4, Pozidriv size 2
ï‚· Operating tool
∅ 5 to 6 ∅ 5 to 6
ï‚· Tightening torque
Nm 0.8 to 1.2 2 to 2.5
ï‚· Conductor cross-sections (min./max.), 1-wire or 2-wire
- Solid mm
2
2 x (0.5 to 1.5)
1)
2 x (0.75 to 2.5)
1)
2 x (1 to 4)
1)
2 x (1 to 2.5)
1)
2 x (2.5 to 10)
1)
- Finely stranded with end sleeve
(DIN 46228 Part 1)
mm
2
2 x (0.5 to 1.5)
1)
2 x (0.75 to 2.5)
2)
2 x (1 to 2.5)
1)
2 x (2.5 to 6)
1)
max. 1 x 10
- AWG cables, solid or stranded AWG 2 x (20 to 14)
1)
1 x 12
1)
2 x (16 to 12)
1)
2 x (14 to 8)
1)
Connection type Spring-loaded connection
ï‚· Operating tool
∅ 3.0 x 0.5
ï‚· Conductor cross-sections (min./max.)
- Solid mm
2
1 x (0.5 to 4) 1 x (1 to 10)
- Finely stranded without end sleeve mm
2
1 x (0.5 to 2.5) 1 x (1 to 6)
- Finely stranded with end sleeve
(DIN 46228 Part 1)
mm
2
1 x (0.5 to 2.5) 1 x (1 to 6)
- AWG cables, solid or stranded AWG 1 x (20 to 12) 1 x (18 to 8)
1)
If two different conductor cross-sections are being connected to one clamping point, both cross-sections must be
located in the range indicated. If identical cross-sections are used, this restriction does not apply.