breaker remains closed after the reclaim timer expires, the Autoreclose cycle is complete, and signals are
generated to indicate that Autor
eclose was successful. These are:
● CB1 Succ 1P AR (Single-phase Autoreclose CB1)
● CB2 Succ 1P AR (Single-phase Autoreclose CB2)
● CB1 Succ 3P AR (Three-phase Autoreclose CB1)
● CB2 Succ 3P AR (Three-phase Autoreclose CB2)
These signals increment the relevant circuit breaker successful Autoreclose shot counters, as well as resetting the
Autoreclose in progress signal.
The relevant circuit breaker successful Autoreclose shot counters are:
● CB1 SUCC SPAR (Single-phase Autoreclose CB1)
● CB1 SUCC 3PAR Shot1 (Three-phase Autoreclose CB1, Shot 1)
● CB1 SUCC 3PAR Shot2 (Three-phase Autoreclose CB1, Shot 2)
● CB1 SUCC 3PAR Shot3 (Three-phase Autoreclose CB1, Shot 3)
● CB1 SUCC 3PAR Shot4 (Three-phase Autoreclose CB1, Shot 4)
● CB2 SUCC SPAR (Single-phase Autoreclose CB2)
● CB2 SUCC 3PAR Shot1 (Three-phase Autoreclose CB2, Shot 1)
● CB2 SUCC 3PAR Shot2 (Three-phase Autoreclose CB2, Shot 2)
● CB2 SUCC 3PAR Shot3 (Three-phase Autoreclose CB2, Shot 3)
● CB1 SUCC 3PAR Shot4 (Three-phase Autoreclose CB2, Shot 4)
Chapter 7 - Autoreclose P54A/B/C/E
176 P54xMED-TM-EN-1