EasyManuals Logo
Home>GE>Relays>P54C

GE P54C User Manual

GE P54C
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #246 background imageLoading...
Page #246 background image
Note:
A minimum v
alue of 8% negative phase sequence current is required for successful operation.
Since sensitive settings have been employed, we can expect that the element will operate for any unbalanced
condition occurring on the system (for example, during a single pole autor
eclose cycle). For this reason, a long time
delay is necessary to ensure co-ordination with other protection devices. A 60 second time delay setting may be
typical.
The following example was recorded by an IED during commissioning:
I
full load
= 500A
I
2
= 50A
therefore the quiescent I
2
/I
1
ratio = 0.1
To allow for tolerances and load variations a setting of 20% of this value may be typical: Therefore set:
I
2
/I
1
= 0.2
In a double circuit (parallel line) application, using a 40% setting will ensure that the broken conductor protection
will operate only for the circuit that is affected. A setting of 0.4 results in no pick-up for the parallel healthy circuit.
Set I
2
/I
1
Time Delay = 60 s to allow adequate time for short circuit fault clearance by time delayed protections.
Chapter 9 - Current Protection Functions P54A/B/C/E
220 P54xMED-TM-EN-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P54C and is the answer not in the manual?

GE P54C Specifications

General IconGeneral
BrandGE
ModelP54C
CategoryRelays
LanguageEnglish

Related product manuals