July 2010 11 – 135
Log files The PROFIBUS diagnosis described is mainly suitable for static failures.
An analysis of sporadic failures is thus difficult.
Experience has shown, however, that sporadic failures account for the mayority of PROFIBUS
errors.
For the analysis of sporadic failures special PROFIBUS log files are suitable which record
important events during start-up and run time.
PBCONFIG_FAIL.LOG
Protocol of the last start of the PROFIBUS system (if the start was aborted due to an error).
PBCONFIG_OK.LOG
Log recording the last successful start of the PROFIBUS system.
PBLOGBOOK.LOG
Log of the PROFIBUS system start indicating the software versions and possible errors.
The log is continuously added to.
As of 1 MB the contents is copied toPBLOGBOOK.LOG.OLD.
REPORT.TXT
Protocol of the last PROFIBUS start (will be overwritten during the next HSCI/PROFIBUS
start.)
REPORT_EXT.TXT
Saves diagnostic messages of the slave. The log is continuously added to, but it is limited to
approx. 1 MB. After the limit has been reached, the “old” diagnostic messages will be moved
to REPORT_EXT.TXT.OLD.
All these files are saved in the path PLC:\PROFIBUS.
For analysis of a PROFIBUS error this file is read out from the control by the TNCremoNT and
are sent to your machine manufacturer or to a HEIDENHAIN service agency.

Table of Contents

Other manuals for HEIDENHAIN ITNC 530

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HEIDENHAIN ITNC 530 and is the answer not in the manual?

HEIDENHAIN ITNC 530 Specifications

General IconGeneral
BrandHEIDENHAIN
ModelITNC 530
CategoryControl Systems
LanguageEnglish

Related product manuals