FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
6 Power-On Commissioning
Copyright © Huawei Technologies Co., Ltd.
243
Procedure
Step 1 Set temperature sensor parameters.
In this example, the temperature sensor is connected to the AI/DI_2 port on the ECC800.
1. Log in to the ECC800 WebUI as an administrator.
2. Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
3. Set Device Type to ECC800, set Device Name to ECC800, and click OK.
4. On the query result tab page, set the new signal name of AI/DI_2 to Temperature and
click Submit.
5. Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_2 Port
Settings.
6. Set Temperature sensor to Enable and click Submit.
7. Confirm that Temperature sensor type is automatically identified as NTC. Ensure that
Temperature power supply is Yes.
Step 2 Check the monitoring functions of temperature sensor.
Table 6-8 Commissioning the sensor
Check Method
Normal Connection Status
View the operating information
about the temperature sensor on
the WebUI.
You can view the current cabinet temperature.
----End
6.3.6.4 Commissioning the Door Status Sensor
Procedure
Step 1 Set door status sensor parameters.
1. Log in to the ECC800 WebUI as an administrator.
2. Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
3. Set Device Type to Independent Deployment AI_DI Unit, set Device Name to
Independent Deployment AI_DI1 Unit, and click OK.
4. On the query result tab page, set the new signal name of AI/DI_1 to Door1 and click
Submit.
Order number of door sensor name is same as cabinet.
5. Choose Monitoring > System > Independent Deployment AI_DI Unit Group >
Independent Deployment AI_DI1 Unit > Running Parameters > AI/DI_1 Port
Settings.

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals